Surge Arrester – V25-B+C3+NPE – OBO

Surge Arrester – V25-B+C3+NPE – OBO

85,00 €

PN: V25-B+C3+NPE

Category:
Brands:

Description

Technical Specifications

Specification Details
Brand OBO Bettermann
Model V25-B+C 3+NPE
Article Number 5094463
EAN 4012195239864
Product Type Combination Lightning Current and Surge Arrester
SPD Type Type 1 + Type 2
Pole Configuration 3+N/PE
Nominal AC Voltage 230 V
Maximum Continuous Operating Voltage 280 V AC
Maximum Continuous DC Voltage 200 V
Lightning Impulse Current 7 kA (10/350 μs)
Voltage Protection Level < 0.9 kV
Lightning Protection Zone LPZ 0→2
Technology Zinc Oxide Varistor
Design Encapsulated, non-blowing
Disconnection Dynamic cut-off device
Connection Pluggable arrester
Status Indicator Optical
Protection Rating IP20
Network Systems TN-S, TT
Operating Temperature -40 °C to +80 °C
Rigid Conductor Cross-Section 2.5–35 mm²
Installation Standard distribution housing / DIN rail
Product Weight Approx. 51 g per unit*

*OBO’s datasheet lists the product weight as 51 kg per 100 pieces, equivalent to approximately 510 g per individual unit; the manufacturer source presents the value in kg/100 pcs.


Ideal Applications

The OBO V25-B+C 3+NPE is suitable for a wide range of three-phase electrical installations, including:

  • Three-phase electrical distribution boards
  • Residential buildings
  • Commercial buildings
  • Industrial facilities
  • Main and sub-distribution systems
  • Building electrical infrastructure
  • Power distribution cabinets
  • Installations supplied by overhead power lines
  • Lightning protection equipotential bonding
  • Electrical systems requiring Type 1+2 surge protection
  • Installations requiring TN-S or TT system compatibility

OBO specifically identifies applications such as buildings supplied by overhead power lines and installations where lightning protection equipotential bonding is required.


Installation and System Integration

The V25-B+C 3+NPE is intended to be integrated into an appropriate low-voltage distribution system and connected according to the applicable electrical installation standards and OBO installation instructions.

Correct conductor sizing, protective bonding, grounding, backup protection, and installation configuration should be selected according to the electrical system and applicable standards.


Why Choose OBO V25-B+C 3+NPE?

The OBO V25-B+C 3+NPE combines Type 1 and Type 2 surge protection with a three-phase + NPE configuration in one compact device. Its 7 kA lightning impulse current capability, <0.9 kV protection level, pluggable construction, optical status indication, encapsulated zinc oxide varistor technology, and TN-S/TT compatibility make it suitable for comprehensive surge protection in three-phase low-voltage distribution systems.

SEO Product Description

OBO V25-B+C 3+NPE is a Type 1+2 combination lightning current and surge arrester designed for three-phase low-voltage electrical installations. With a 3+N/PE configuration, 230 V nominal voltage, 280 V maximum continuous operating voltage, 7 kA lightning impulse current, voltage protection level below 0.9 kV, and IP20 protection rating, the V25-B+C 3+NPE provides reliable protection against lightning-related and transient overvoltages. The device features an encapsulated zinc oxide varistor, dynamic disconnection, pluggable construction, optical function indication, and compatibility with TN-S and TT electrical systems. It is suitable for residential, commercial, and industrial distribution boards and other electrical installations requiring combined Type 1+2 surge protection.


Datasheet